CABLING PROPERTIES |
|
Standardization |
IEC 60794-2 |
Construction |
I-FN(ZN)H or I-FN(ZN)HH cable incl. Ø3.0mm 12 fiber sub-units |
Buffer type |
N/A |
Strength member |
Non-metallic aramid yarns |
Jacket material |
FRNC (TPE-0), LSZH/LS0H |
Jacket dimensions [mm] |
3.0 (1x12) 8.9 (up to 4x12), 13.1 (8x12), 16.5 (12x12) |
Min. bend radius (static) [mm] |
130 (up to 4x12), 250 (up 12x12), (acc. to IEC 60794-1-21 E11) |
Min. bend radius (dynamic) [mm] |
200 (up to 4x12), 330 (up 12x12) (acc. to IEC 60794-1-21 E11) |
Applicable tensile load (long term) [N] |
800 (up to 4x12), 1000 (up 12x12) (acc. to IEC 60794-1-21 E1) |
Crush resistance (long term) [N/dm] |
1000 |
FIRE BEHAVIOUR |
|
Fire load [MJ/m] |
0.14 |
Temperature range (operation) [°C] |
-5 to +60 (acc. to IEC 60794-1-22 F1) |
Flame retardancy |
IEC 60332-1-2, IEC-60332-3-22 Cat.A |
Smoke density |
IEC 61034 |
Absence of halogen |
IEC 60754-1 |
Acidity of combustion gases |
IEC 60754-2 |
CODING & TERMINATION |
|
Colour coding of cable jacket |
OM3: aqua, OM4: heather violet, SM: yellow |
Colour coding of connectors and boots |
OM3/PC: aq, OM4/PC: h.violet, SM/UPC: bl, SM/APC8°: gn |
Polarity |
A, B or C |
Available connectors |
MPO, MTP |
Max. applicable connector load [N] |
100N |
Max. mating cycles |
500 |
OPTICAL PERFORMANCE |
|
Endface geometry |
100% acc. to IEC 61755-3-1/2 |
Instertion loss (acc to. IEC 61753) [dB] |
0.15 typ, 0.30dB max (100% testing acc. to IEC 61300-3-4 Method B |
Return loss (MM PC) [dB] |
-35.0 max (100% testing acc. to IEC 61300-3-6) |
Return loss (SM UPC) [dB] |
-55.0 max (100% testing acc. to IEC 61300-3-6) |
Return loss (SM APC8°) [dB] |