FiberOptic Kft.

A-DQ(ZN)B2Y Outdoor Loose Tube Assemblies

  • Application: Outdoor
  • Mode: G50/125 OM3, G50/125 OM4, E09/125 G.652.D, E09/125 G.657.A1
  • Termination: DIN (LSA), E2000 (LSH), FC, LC, MPO, MTP, MU, SC, ST
  • Fibers: 4, 6, 8, 12, 16, 24, 48, 96, 144

CABLING PROPERTIES

Standardization

IEC 60794-2

Construction

A-DQ(ZN)B2Y central (up to 24x) or multi (up to 48x) tube cable

Buffer type

N/A

Jacket material

HDPE

Strength member

Waterblocking fiberglass

Jacket dimensions [mm]

7.2 (up to 12x), 7.9 (up to 24x), 10.5 (up to 48x), 13.8 (up to 96x), 14.0 (up to 144x)

Min. bend radius (static) [mm]

15x outer Ø (acc. to IEC 60794-1-21 E11)

Min. bend radius (dynamic) [mm]

20x outer Ø (acc. to IEC 60794-1-21 E11)

Applicable tensile load (long term) [N]

1000 (acc. to IEC 60794-1-21 E1)

Crush resistance (long term) [N/dm]

2000 (up to 12x0.9), 1500 (24x0.9) (acc. to IEC 60794-1-21 E3)

 

FIRE BEHAVIOUR

Temperature range (operation) [°C]

-40 to +70 (acc. to IEC 60794-1-22 F1)

CPR classification (Euroclass)

Fca

 

CODING & TERMINATION

Colour coding of cable jacket

Black

Colour coding of terminated units

OM3: aq, OM4: h.violet, SM: ye, Outdoor: black, Armored: metal

Colour coding of connectors and boots

OM3/PC: aqua, OM4/PC: h.violet SM/UPC: blue, SM/APC8°: green

Available connectors

LSA (DIN), E2000 (LSH), FC, LC, MU, MPO, MTP, SC, ST

Max. applicable connector load [N]

100N

Max. mating cycles

500

 

OPTICAL PERFORMANCE

Endface geometry

100% acc. to IEC 61755-3-1/2

Instertion loss (acc to. IEC 61753) [dB]

0.15 typ, 0.30dB max (100% testing acc. to IEC 61300-3-4 Method B

Return loss (MM PC) [dB]

-35.0 max (100% testing acc. to IEC 61300-3-6)

Return loss (SM UPC) [dB]

-55.0 max (100% testing acc. to IEC 61300-3-6)

Return loss (SM APC8°) [dB]

-65.0 max (100% testing acc. to IEC 61300-3-6)